Lead, Lag and PID Compensators: GATE ECE practice questions with solutions
This topic covers lead and lag networks, maximum phase lead, PID zeros, PD pole placement and Ziegler-Nichols tuning. The 15 original questions follow the GATE EC format: 9 MCQ, 2 MSQ and 4 NAT, from 5 easy, 7 medium and 3 hard.
Three ideas to know:
- The peak lead sits at the geometric mean of the two corner frequencies.
- The pole of a lead network lies 1/α times farther from the origin than its zero.
- Find the ultimate gain and period from the Routh array, then apply the tuning table.
It helps GATE EC and ECE students revising Control Systems for the exam or a semester test. Helpful background: Lead compensator formulas and Lead compensator frequency response. Start with the 5 easy questions, then work up to the 3 hard ones.
Related
Q.1
EasyMCQ1 mark
The compensator Gc(s) = (1 + 0.4s)/(1 + 0.1s) gives its maximum phase lead at
Show answer and solutionHide answer and solution
Answer: (B)
Key idea: The peak lead sits at the geometric mean of the two corner frequencies.
1. Corners: zero at 1/0.4 = 2.5 rad/s, pole at 1/0.1 = 10 rad/s. 2. ωm = √(2.5 × 10) = 5 rad/s.
Common mistake: Taking the arithmetic mean (2.5 + 10)/2 = 6.25 rad/s, option (C).
You need: Lead compensator frequency response
Q.2
EasyMCQ1 mark
The main purpose of a lag compensator placed well below the gain crossover frequency is that it
Show answer and solutionHide answer and solution
Answer: (A)
Key idea: Lag improves accuracy; lead improves speed and margins.
1. A lag network has more gain at low frequency than at high frequency.
2. Placed far below crossover, it raises the error constants while leaving the phase near crossover almost unchanged.
3. It tends to lower the bandwidth, not raise it.
Common mistake: Swapping the roles of lead and lag and choosing (B).
You need: Lead and lag networks
Q.3
EasyNAT1 mark
The maximum phase lead of Gc(s) = (1 + 0.4s)/(1 + 0.1s) is ______ degrees (round to one decimal place).
Numerical answer: type a number.
Show answer and solutionHide answer and solution
Answer: 36.9 (accepted 36.8 to 36.9)
Key idea: The peak lead depends only on the ratio α of pole and zero time constants.
1. Write it as (1 + Ts)/(1 + αTs) with T = 0.4 s and α = 0.25. 2. sin φm = (1 − α)/(1 + α) = 0.75/1.25 = 0.6. 3. φm = sin⁻¹(0.6) = 36.87°.
Common mistake: Using sin φm = 1 − α = 0.75 gives 48.6°.
You need: Lead compensator formulas
Q.4
EasyMCQ1 mark
A PID controller has Kp = 2, Ki = 4 and Kd = 0.5, so C(s) = Kp + Ki/s + Kd s. The zeros of C(s) are at
Show answer and solutionHide answer and solution
Answer: (C)
Key idea: A PID controller adds a pole at the origin and two zeros set by the three gains.
1. C(s) = (0.5s² + 2s + 4)/s.
2. Divide by 0.5: s² + 4s + 8 = 0. 3. s = −2 ± j2.
Common mistake: Writing the numerator as Kd s² + Kp s + Ki with the gains placed wrongly as s² + 2s + 4 gives −1 ± j√3, option (A).
You need: PID transfer function
Q.5
EasyMCQ1 mark
A type 0 plant under proportional control has a non-zero step error. The proportional controller is replaced by a PI controller and the loop stays stable. The result is that
Show answer and solutionHide answer and solution
Answer: (D)
Key idea: Each integrator raises the type by one.
1. The PI controller adds a pole at s = 0.
2. The loop becomes type 1.
3. A stable type 1 loop has zero step error and a finite ramp error.
Common mistake: Jumping one order too far and expecting zero ramp error, option (B).
You need: System type, PI control
Q.6
MediumMCQ1 mark
A passive lead network has R₁ = 100 kΩ in parallel with C = 1 µF as the series element and R₂ = 25 kΩ from output to ground. Its transfer function has
Show answer and solutionHide answer and solution
Answer: (A)
Key idea: The pole of a lead network lies 1/α times farther from the origin than its zero.
1. Gc = α(1 + Ts)/(1 + αTs) with T = R₁C = 0.1 s and α = R₂/(R₁ + R₂) = 0.2.
2. Zero at −1/T = −10.
3. Pole at −1/(αT) = −1/0.02 = −50.
Common mistake: Taking the pole at −1/(R₂C) = −40, option (C).
You need: Lead network circuit
Q.7
MediumNAT1 mark
The high-frequency gain of the lag compensator Gc(s) = (1 + 10s)/(1 + 50s), relative to its DC gain, is ______ dB (round to two decimal places).
Numerical answer: type a number.
Show answer and solutionHide answer and solution
Answer: −13.98 (accepted −14.1 to −13.9)
Key idea: A lag network attenuates high frequencies by the ratio of its time constants.
1. DC gain: 1.
2. High-frequency gain: 10/50 = 0.2. 3. 20 log₁₀ 0.2 = −13.98 dB.
Common mistake: Using 10 log₁₀ instead of 20 log₁₀ gives −6.99 dB.
You need: Decibels, lag networks
Q.8
MediumMCQ2 marks
A lead compensator (1 + Ts)/(1 + αTs) must supply a maximum phase lead of 30°. The required α is
Show answer and solutionHide answer and solution
Answer: (C)
Key idea: Invert sin φm = (1 − α)/(1 + α).
1. α = (1 − sin φm)/(1 + sin φm). 2. sin 30° = 0.5. 3. α = 0.5/1.5 = 1/3.
Common mistake: Using α = 1 − sin φm = 0.5, option (A).
You need: Lead compensator formulas
Q.9
MediumMSQ2 marks
Which of the following statements about the three PID terms are correct?
One or more options are correct.
Show answer and solutionHide answer and solution
Answer: (A), (B) and (C)
Key idea: Integral adds lag and accuracy; derivative adds lead and noise sensitivity.
1. Kd s has +90° phase, which adds lead and damping.
2. Ki/s raises the type by one, so a stable loop has zero step error. 3. |Kd jω| grows with ω, so noise is amplified.
4. Ki/s has −90° phase: it adds lag, so (D) is false.
Common mistake: Thinking integral action improves phase margin and selecting (D).
You need: PID control
Q.10
MediumMCQ2 marks
A PD controller Kp + Kd s drives the plant 1/[s(s + 2)] in a unity negative feedback loop. The closed loop must have ωn = 4 rad/s and ζ = 0.75. The required gains are
Show answer and solutionHide answer and solution
Answer: (B)
Key idea: The plant's own damping term adds to the derivative gain.
1. Characteristic equation: s² + (2 + Kd)s + Kp = 0.
2. Kp = ωn² = 16. 3. 2 + Kd = 2ζωn = 6, so Kd = 4.
Common mistake: Setting Kd = 2ζωn = 6 and forgetting the plant's 2s, option (A).
You need: Second-order pole placement
Q.11
MediumNAT2 marks
A loop with plant G(s) = 20/[s(s + 4)] has Kv = 5. A lag compensator Gc(s) = (s + 0.1)/(s + p) is added to raise Kv to 50 without moving the crossover much. The pole p must be ______.
Numerical answer: type a number.
Show answer and solutionHide answer and solution
Answer: 0.01
Key idea: A lag network's DC gain is the zero-to-pole ratio z/p.
1. The lag network multiplies Kv by its DC gain 0.1/p. 2. 5 × 0.1/p = 50. 3. p = 0.01.
Common mistake: Multiplying instead of dividing, p = 10 × 0.1 = 1, which lowers Kv instead.
You need: Lag compensation, velocity error constant
Q.12
MediumMCQ2 marks
The PI controller C(s) = 5 + 2/s has its zero at
Show answer and solutionHide answer and solution
Answer: (D)
Key idea: The PI zero is at −Ki/Kp.
1. C(s) = (5s + 2)/s = 5(s + 0.4)/s.
2. The zero is at s = −Ki/Kp = −0.4.
Common mistake: Inverting the ratio, −Kp/Ki = −2.5, option (A).
You need: PI controller form
Q.13
HardMCQ2 marks
A plant G(s) = 12.5/s² (zero phase margin) is compensated with the lead network Gc(s) = (1 + 0.4s)/(1 + 0.1s). The phase margin of Gc(s)G(s) is closest to
Show answer and solutionHide answer and solution
Answer: (B)
Key idea: A lead network also raises the gain, which moves the crossover; here it moves it exactly to ωm.
1. The lead peaks at ωm = 5 rad/s with gain 1/√α = 2 and phase 36.87°. 2. |G(j5)| = 12.5/25 = 0.5, so |GcG| = 2 × 0.5 = 1: the new crossover is exactly 5 rad/s.
3. Phase = −180° + 36.87°, so PM = 36.9°.
Common mistake: Keeping the uncompensated crossover √12.5 = 3.54 rad/s and adding the lead phase there gives about 35.3°, option (A).
You need: Lead compensator design, phase margin
Q.14
HardNAT2 marks
A plant G(s) = 2/[(s + 1)(s + 2)(s + 4)] is under proportional control K in a unity negative feedback loop. Using the Ziegler-Nichols ultimate-gain rules (PID: Kp = 0.6 Ku, Ti = Pu/2, Td = Pu/8), the proportional gain Kp is ______.
Numerical answer: type a number.
Show answer and solutionHide answer and solution
Answer: 27
Key idea: Find the ultimate gain and period from the Routh array, then apply the tuning table.
1. Characteristic equation: s³ + 7s² + 14s + 8 + 2K = 0.
2. Marginal: 7 × 14 = 8 + 2K, so Ku = 45.
3. Oscillation at ω = √14 = 3.74 rad/s, so Pu = 1.68 s.
4. Kp = 0.6 × 45 = 27.
Common mistake: Forgetting the plant gain 2 (using 7 × 14 = 8 + K) gives Ku = 90 and Kp = 54.
You need: Routh array, Ziegler-Nichols tuning
Q.15
HardMSQ2 marks
For the lag compensator Gc(s) = (s + 0.2)/(s + 0.02), which of the following statements are correct?
One or more options are correct.
Show answer and solutionHide answer and solution
Answer: (A), (B) and (D)
Key idea: Lag networks mirror lead networks: same geometric-mean peak, opposite sign.
1. DC gain 0.2/0.02 = 10.
2. As s → ∞ the gain tends to 1.
3. The peak lag is at √(0.2 × 0.02) = 0.063 rad/s, so (C) is false. 4. sin φ = (10 − 1)/(10 + 1) = 0.818, φ = 54.9° of lag.
Common mistake: Using the arithmetic mean (0.2 + 0.02)/2 = 0.11 rad/s for the peak, option (C).
You need: Lag compensator frequency response